Our Products
Our Products
For optimal performance of the engine, it is suggested to run the genset / generator at loads in excess of 25%
GENERATOR SET SPECIFICATIONS |
|
Model | C750D5P |
Duty | Prime |
Power Rating kVA / kWe | 750/600 |
No. of Phases | 3 |
Output Voltage and Frequency (V and Hz) | 415 V, 50 Hz |
Power Factor | 0.8 (lagging) |
Current (A) | 1043 |
RPM | 1500 |
ENGINE SPECIFICATIONS |
|
Make | Cummins |
Model | KTA38-G10 |
MoEF Certified Power (hp) | 987 |
Required Power for Rated kVA (hp) | 891 |
Cooling | Liquid cooled (Distilled Water +DCA2) |
Aspiration | Turbocharged Aftercooled |
No. of cylinders | 12, Vee |
Bore (mm) x Stroke (mm) | 159 x 159 |
Compression ratio | 16.7:1 |
Displacement (litre) | 38 |
Fuel | High Speed Diesel |
Fuel consumption @75% load with radiator and fan* (litre/hr) | 130.4 |
Fuel consumption @100% load with radiator and fan* (litre/hr) | 165 |
Performance class of generator set | ISO 8528-5 G2 |
Starting system | 24 V DC Electrical |
Lube oil specification | CH4 15W40 |
Lube oil sump capacity, High-Low level (litre) | 140 - 114 |
Total lubrication system capacity (litre) | 155 |
Lube oil consumption @ full load** (litre/hr) | 0.24 |
Total coolant capacity (litre) | 330 |
No. of banks x Exhaust pipe size (inch) | 2 x 8 |
Total wet weight (Engine+Radiator)## (kg) | 5800 |
Length x Width x Height (Engine) (mm) | 2269 x 1436 x 1764 |
Mean piston speed (m/s) | 7.95 |
Combustion air intake @100% load (±5%) (cfm) | 2055 |
Exhaust Temperature (°C) Alternator Specification | 406 |
ALTERNATOR SPECIFICATIONS |
|
Make | Stamford (CGT) |
Alternator frame | HCI634W |
Enclosure | IP 23 |
Voltage regulation (Max.) | ±1% |
Class of Insulation | H Class |
Winding Pitch | 2-Mar |
Stator Winding | Double layer lap |
Rotor | Dynamically balanced |
Wave form distortion | No load < 1.5 %, Non distorting balanced linear load < 5 % |
Maximum Unbalanced Load across phases# | less than or equal to 25% |
Telephonic Harmonic factor | < 2% |