1250kVA - 1500kVA GENERATOR SET SPECIFICATIONS / GENERATOR ON RENT |
||
Model | C32 | |
Prime Power Rating kVA | 1250 | |
Output Voltage and Frequency | 415 Volts, 50 Hz | |
Power Factor | 0.8 (lag) | |
No. of phases | 3 phase |
ENGINE SPECIFICATIONS |
||
Make | CAT | |
Model | KTA 50 G3 | |
No. of cylinders | 16 ‘Vee’ | |
Aspiration | Turbocharged-Aftercooled | |
Bore x Stroke | 159 mm x 159 mm | |
Displacement | 50.3 ltrs | |
Output - Prime | 1470 bhp (1097 kWm) | |
Fuel consumption @ 75% load with Radiator & Fan | 190.8 ltr/hr | |
Fuel consumption @ 100% load | 251.8 ltr/hr | |
Typical oil consumption @ 100% load | 0.3 ltr/hr | |
Total wet weight ( engine + radiator) | 6824 kg | |
Length x Width x Height (engine) | 2978 x 2080 x 1780 mm | |
Compression Ratio | 13.9 : 1 | |
Piston Speed | 7.95 m/s | |
Governor / Class | Electronic / A1 | |
Lubricating oil sytem capacity | 177 ltrs | |
Coolant capacity (engine + radiator) | 440 ltrs | |
Combustion air intake @ 100% load (+/- 5%) | 81.6 m3/min | |
Fan air flow across radiator | 27357 ltrs/sec | |
Exhaust Temperature | 529 oC |
ALTERNATOR SPECIFICATIONS |
||
Make | Stamford | |
Frame size / Model No. | HCK6Z | |
Voltage Regulation | 0.50% | |
Insulation | Class H | |
Standard Enclosure | IP 23 | |
Winding Pitch | 2 / 3 Pitch | |
Stator Winding | Double layer lap | |
Rotor | Dynamically balanced | |
Wave form distortion | No load < 1.8 %, non distorting balanced linear load < 5 % |
|
Telephone Interference Factor | Better than 50 | |
Total Harmonic Factor | Better than 2% |